High Voltage 3.6/6, 6/10, 8.7/15 Power Cable:
CABLE DESIGNATION
3.6/6kV SPYCB(Y), TPYC(Y), FA-SPYCB(Y), FA-TPYC(Y)
6/10kV SPYCB(Y), TPYC(Y), FA-SPYCB(Y), FA-TPYC(Y)
8.7/15kV SPYCB(Y), TPYC(Y), FA-SPYCB(Y), FA-TPYC(Y)
APPLICATION STANDARD
- Design guide : IEC 60092-350, -354
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A (FA-Type)
- Cold bend/impact : CSA 22.2 No. 03 (-35 ℃) (Cold Type)
- Max. conductor temperature : 90 ℃
Technical Data:
1. CABLE TYPE 3.6/6kV (FA-)SPYCB, 3.6/6kV (FA-)SPYCBY
No. of Cores:1 core
Nominal Area:10,16,25,35,50,70,95,120,150,185,240,300,400,500,630.
2. CABLE TYPE: 3.6/6kV (FA-)TPYC, 3.6/6kV (FA-)TPYCY
No. of Cores:3 core
Nominal Area:10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300.
3.CABLE TYPE: 6/10KV (FA-)SPYCB, 6/10KV (FA-)SPYCBY
No. of Cores:1 core
Nominal Area:16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630.
4. CABLE TYPE: 6/10KV (FA-)TPYC, 6/10KV (FA-)TPYCY
No. of Cores:3 core
Nominal Area(mm2):16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300.
5. CABLE TYPE: 8.7/15kV (FA-)SPYCB, 8.7/15kV (FA-)SPYCBY
No. of Cores:1 core
Nominal Area(mm2):25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630.
6. CABLE TYPE: 8.7/15kV (FA-)TPYC, 8.7/15kV (FA-)TPYCY
No. of Cores:3 core
Nominal Area(mm2):25, 35, 50, 70, 95, 120, 150, 185, 240, 300.
| Classification | Code | Construction Detail | 
| 1. Conductor | T(S) | Stranded tinned annealed copper wires as per IEC 60228, Class B | 
| 2. Conductor screen | Semi-conducting layer (tape/compound) | |
| 3. Insulation | P | EPR as per IEC 60092-351. | 
| 4. Insulation screen | .Non-metallic part :
  Semi-conducting layer(tape/compound). .Metallic part : Copper tape. .A suitable separator tape(s) may be applied over the metallic part.C14 | |
| 5.Cabling | .Three insulation screened
  conductors shall be cabled. .Flame retardant & non-hygroscopic fillers may be used. .Suitable tape(s) may be applied on the cabled core. | |
| 6. Sheath | Y | ST2(PVC) as per IEC 60092-359. | 
| 7. Armor | C (CB) | .Braid of copper alloy wires
  (-CB type) or galvanized steel wires (-C type). .Coverage density is minimum 90% | 
| 8. Paint | .The red paint shall be painted
  uniformly on the steel wire braid .“CB” Type or Protective covering Type, paint is dispensable. | |
| 9. Protective covering | Y | ST2 (PVC) as per IEC
  60092-359. Outer sheath color : Red | 
| 10. Core identification | 3C : Red, Yellow, Blue | 

 
                                 
                                



